Nationwide Institute of Neurosciences and the elevator of the hospital Dr. Well being Minister. The investigation report on Samant Lal Sen‘s detention has been revealed. Investigating the incident, the investigation committee discovered proof of ‘negligence’ in a number of issues, together with lack of required coaching of Automated Rescue Gadget (ARD) and carry operators.
On Tuesday (Might 21), the investigation committee submitted its report back to the Ministry of Well being and Household Welfare.
In accordance with the statement of the report, the 1,000 kg capability elevator concerned within the accident is of Sigma (Manufactured by OTIS Elevator, Korea) model by ‘Man Bangladesh Restricted’. The carry was inaugurated on the Nationwide Institute of Neurosciences and Hospital on September 12, 2012. Since then it has been used for about 12 years. The identical group is entrusted with month-to-month servicing and upkeep in the course of the present monetary yr for clean operation of the carry. They’re servicing frequently.
Through the inspection of the investigation committee, no downside was discovered within the motion of the elevator, however after reviewing the statements and different data of varied folks associated to the elevator, a number of errors had been discovered. These are:
1. Public Works E/M Division-7, Dhaka Govt Engineer, involved Sub-Divisional Engineer (E/M) and anxious Sub-Assistant (E/M) issued directions to the carry upkeep institutions however lack of correct direct work supervision was noticed.
2. The Automated Voltage Regulator (AVR) gadget put in to supply secure voltage energy to function the carry is inoperative.
3. There isn’t a Automated Rescue Gadget (ARD) put in to routinely take the carry to the closest ground stage in case of energy failure throughout carry operation or if the carry stops between two flooring for every other motive.
4. The management panel thought-about as the principle controller of the elevator is made up of microprocessors and varied semiconductors, that are stored on the specified temperature. Air coolers are put in within the management room. Air cooler is current within the management room however is in ineffective situation.
5. From the assertion of varied folks associated to the carry, it’s evident that the overload sensor didn’t work even when there have been extra folks within the carry. As a consequence of voltage fluctuation or every other fault within the energy provide system, the change or controller to cease on the specified stage didn’t work correctly and couldn’t cease on the specified stage.
6. Units and capabilities which might be required to be examined on a month-to-month foundation in accordance with the related carry producer’s directions haven’t been correctly examined.
7. There isn’t a proof of sole reliance on servicing and upkeep companies and presence of Public Works Division officers throughout work hours.
8. Operation and upkeep manuals, grievance registers, servicing, restore and upkeep historical past books and so forth. will not be maintained on the website.
9. Operators are employed regardless of not having the required coaching of carry operators. Even after recruitment, correct coaching was not supplied.
By the way, after attending the dialogue assembly on the event of the Nice Independence Day on March 31, Well being Minister Dr. Samant Lal Sen together with 9 to 10 senior officers of the hospital took the carry to go down from the tenth ground to the bottom ground. Because the elevator began transferring and neared the second ground, they heard a noise. Then he heard one other noise because the elevator stopped.
The doorways didn’t open routinely after the elevator stopped on the backside. Later the carry operator on responsibility with the assistance of the operator on responsibility of the adjoining carry arranges to open the door after 7 to eight minutes. After opening the door, it’s seen that the carry stops far beneath the ground reasonably than on the designated floor ground stage. On this state of affairs, with the assistance of instruments (momentary association for sitting) decided by the carry operator, the minister and different officers staying within the carry had been introduced out. Well being Minister expressed anger and displeasure on this incident.